Generator control system
Based on VCS183
DS_VCS183
Page 8
Rev. 06
www.fischerpanda.com
©Fischer Panda generators Inc.
reference to programing data is made it will be marked with “Pxx” referencing t
o parameter xx out of
Table 8: Programing parameters:
It should be noted that any sensing input (digital or analog) that is disabled in the programing data of
the VCS will cause the control system to assume that sensor reporting “
non-critica
l” status, regardless of
actual (true) sensor data. Sensors may be individually enabled or disabled (P62 and P63).
Functional description
Minimum configuration
A “complete system” is considered to have as a minimum configuration one control sy
stem VCS183, one
current sensing device CT186, one connection board KL188 and at least one panel GP178. It is further
assumed to be wired as per wiring diagram D00037, be connected to a charged battery and have good
fuses on board KL196.
Powering up the control system
The control system may be in one of the below 3 modes:
•
Not powered at all (Battery power disconnected): It will obviously not work in this mode
•
Low power mode: VCS183 and CT186 are in hibernating mode, total current draw is below
10mA
•
Fully on: All components fully operational
After turning battery power on the control system will first enter “Fully On” mode but then, without any
further user interaction within approx. 25sec, will transition to low power mode.
Transitioning between Fully On and Low Power mode is under user control either locally or via remote
input.
•
Local: Button S1 on the control panel faceplate will toggle between these 2 modes
•
Remote: Via terminal J1 pin 5 on the control panel (
Current sensing device CT186xxx
With a faulty current sensing device connected, monitoring functionality is restricted and generator
operation is considered emergency operation; output power and output current cannot be sensed and
therefore this emergency operation poses the risk of overloading the generator. The only limiting factor
that provides some protection against overloading the generator is the coil temperature. For this reason
such emergency operation shall be restricted to an absolute minimum and the user is required to
contact Fischer Panda Service immediately.
Operational status of the current sensing device is indicated by 2 LEDs. For details see
Transitioning from low power mode to regular operational mode
A control system wired as described above (whether CT186xxx or CT195xxx is functional or not) will
power up immediately after applying battery power. It will then check data communication on the CAN