Generator control system
Based on VCS183
DS_VCS183
Page 25
Rev. 06
www.fischerpanda.com
©Fischer Panda generators Inc.
o
Point of connection for the user is the terminal block underneath CT186
o
Re-arrange output jumpers for 120/240V configuration on output terminal block as per
wiring diagram D00037
o
Make sure all 4 wires (L1, L2, N1, N2) are wired to the output terminal block
o
Verify correct connection of PE on output terminal block
•
For generators with nominal output power up to 9kVA
o
Point of connection for the user is J3 on CT186
o
Make sure connector J6 on CT 186 is not jumped. See
Figure 7: Terminal J6 on CT186
o
Make sure one of the neutral terminals (N1 or N2) is connected to PE
o
Output power 2x120V is available between L1/L2 and the other neutral terminal
o
Output power 240V is available between L1 and L2
For 120V configuration:
•
Control board VCS183 needs to be programmed for 120V configuration. See
Select coils to be in parallel.
•
Generator coils need to be connected as indicated in
•
For generators with nominal output power 12kVA or higher:
o
Make sure connector J6 on CT 186 is not jumped. See
Figure 7: Terminal J6 on CT186
Point of connection for the user is the terminal block underneath CT186
o
Re-arrange output jumpers for 120V configuration on output terminal block as per
wiring diagram D00037
o
Make sure all 4 wires (L1, L2, N1, N2) are wired to the output terminal block
o
Verify correct connection of PE on output terminal block
•
For generators with nominal output power up to 9kVA
o
Point of connection for the user is J3 on CT186
o
Jump connector J6 on CT 196 using an AWG6 wire
Figure 7: Terminal J6 on CT186
o
Make sure one of the neutral terminals (N1 or N2) is connected to PE
o
Output power (120V) is available between either one of the terminals L1 or L2 and the
other neutral terminal
Interfacing to communication, sensing and auxiliary inputs
For description of communication and auxiliary
inputs reference is made to
Communication and auxiliary connections on
CT186
Pin numbering on each connector is always
from left to right, seen from the board edge
that
the connector lines up with.
Communication interface
Connectors J1 and J2 serve as power supply and communication interface. Signals on these connectors
are:
•
Pin 1: Power supply, positive
o
J1: Input from connection board KL188, fused 5A / F3 on KL188
Figure 8: Communication and auxiliary connections on
CT186