Generator control system
Based on VCS183
DS_VCS183
Page 20
Rev. 06
www.fischerpanda.com
©Fischer Panda generators Inc.
Bit
Meaning
Remark
ST02
VCS is not programmed or not calibrated
ST03
External stop switch on VCS is active
As per ABYC requirement. Local switch for disabling
the generator is set into “Disable”
ST04
Current sensing device reads >130°C on one or both
terminal temperature sensors
Miss-connection of generator output
ST05
Battery voltage too low to perform start attempt
Internal threshold, not programmable
ST06
Water leak sensor tripped
Will not be set if sensor is disabled
ST07
Start attempt failed
ST08
Cannot stop engine
Fault on stop solenoid.
ST10
Maximum number of consecutive failed starts achieved
ST11
Unexpected engine stop
ST12
Missing both, cylinder head and coolant in temperature
sensor
Will not be triggered if sensor is not enabled
ST13
Missing sensor for exhaust elbow
Will not be triggered if sensor is not enabled
ST14
One of the glow plugs is in SC or the fuel pump is in short-
circuit to ground
Will not reset other than through power cycle
ST15
Cranking gear or run solenoid is in short-circuit to ground
Will not reset other than through power cycle
ST16
Stop solenoid is in short-circuit to ground
Will not reset other than through power cycle
ST17
Fire boy triggered. (connected to one of the control panels)
ST18
Engine stop caused by losing communication
ST19
Supply output to oil pressure sensor out of range
Will be ignored if oil pr. Sensor is disabled
ST20
Hardware configuration mismatch
Generator power beyond capabilities of CT board
ST21
Start/stop conflict
Static and dynamic control inputs in conflict with each
other
ST22
Remote start request denied or timed out
Static remote start on control panel did not get the
generator started. User interaction is required
ST23
Oil pressure reading is not plausible
ST24
Remote control input conflict
Panel with static remote control input was turned off
or lost its static input capability
Program data in the VCS
All relevant operational parameters (thresholds, system configuration, control parameters…) are
programmed in the VCS and accessible to the user via the panel. Such access is code protected and
described in more detail in the section of this document that refers to the control panel. Date and time
of last access to program data will be logged in control board memory. Programing parameters are listed
in below table:
Table 8: Programing parameters:
Field Data
Bits
Unit
0
Idle speed
16
1rpm
1
Nominal speed
16
1rpm
2
Nominal AC voltage
16
0.1V
3
Time slot for PID control algorithm
16
1ms
4
Proportional constant Kp
16
X0.01
5
Integral constant Ki
16
X0.01
6
Derivative constant Kd
16
X0.01
7
Maximum integral part
16
n/a
8
Idling time
8
1s
9
Maximum cranking time
8
1s
10
AC voltage high, warning threshold
16
0.1V