Generator control system
Based on VCS183
DS_VCS183
Page 22
Rev. 06
www.fischerpanda.com
©Fischer Panda generators Inc.
Field Data
Bits
Unit
56
Resistance at full tank
16
1Ω
57
Resistance at empty tank
16
1Ω
58
Cooling down temperature threshold (Cyl. Head)
8
1K
(a)
59
Cooling down time threshold
8
1 min
60
Act position for cranking
8
1%
61
Max. actuator position while cranking / idling
8
1%
62
Generator configuration bits
32
n/a
63
Sensor configuration bits
32
n/a
64
Maximum plausible oil pressure
8
0.1bar
65
Poles
8
n/a
66
Current on gnd bk output, warning
8
10mA
67
Current on gnd bk output, shutdown
8
10mA
68
Delay shutdown max-current on gnd bk output
8
100ms
69
Absolute max. exhaust temp. during warm-up
8
1°C
70
Fuel priming time
8
1s
71
Absolute maximum cylinder head temperature threshold
8
1°C
72
Service notifications enabled in VCS
32
n/a
73
Actual time / date **
32
RTC