![Fischer Panda 15 mini PMS Digital Скачать руководство пользователя страница 103](http://html1.mh-extra.com/html/fischer-panda/15-mini-pms-digital/15-mini-pms-digital_manual_2294276103.webp)
Generator Faults
12.8.20
Kapitel/Chapter 8: Generator Faults - Seite/Page 103
8.4 Troubleshooting Table and Flowchart
8.4.1 Generator output voltage too low
8.4.2 Generator voltage too high
8.4.3 Generator voltage fluctuates
8.4.4 Generator not able to start electric motor
8.4.5 Diesel motor fails to start
8.4.6 Starter is turning motor, but fails to start
Cause
Solution
Generator is overloaded.
Reduce the electrical load (switch off load)
Motor is not reaching the rated rpm.
Refer to „motor faults“ section.
Defective capacitor(s).
Check capacitors and replace if necessary.
Cause
Solution
Over-energizing due to wrong capacitors.
Check capacitors type and replace if necessary.
Cause
Solution
1. Disturbances on the electrical system/user side.
2. Motor disturbances.
1. Check if electrical load is fluctuating.
2. Refer to section: „Motor runs irregular“.
Cause
Solution
If the generator is unable to supply enough power to start an electric
motor 1-phase, it is usually because the motor draws too much current
during starting process.
Check the motor's current draw required for starting (switch to 3-phase,
if possible). This could be remedied by providing stronger capacitors or
installing an optional „Easy Start Booster Set“.
Enquire at your nearest Panda dealer or directly at the manufacturer.
Cause
Solution
Starter battery switched „OFF“.
Check position of battery switch and switch „ON“ (if installed).
Starter battery voltage insufficient (battery too weak).
Inspect battery terminals and cables for a good electrical connection
(Inspect against corrosion, tattered wires, etc.).
Starting current disrupted.
During the normal starting process, the battery voltage drops to 11 V
with a fully charged battery. If the voltage does not drop during starting,
the electrical connection is faulty. If the battery voltage drops lower than
11 V, then the battery has been discharged.
Cause
Solution
Fuel pump not working.
Check fuel-filter and pump: clean if necessary.
Lack of fuel.
Check fuel supply.
Glow-plugs not working correctly.
Check glow plugs and heating time.
Too much air in fuel lines.
Test fuel system for leakage. Bleed air from fuel system (refer to section
„Bleeding Air from Fuel System“).
Fuel-filter blocked.
Replace fuel filter.