60
£
EK24
Lead Lag Status
0 - Boiler sequencing inactive
1 - Boiler held off via sequence control
2 - Boiler in standby via sequence control.
3 - Boiler modulating via sequence control.
4 - Boiler is lead via sequence control
EK25
Burner status
Status of the start-up sequence.
Refer to Gas safety valve proving sequence for details.
EK26
Valve Prove Status
Status of the valve proving sequence.
Refer to Gas safety valve proving sequence for details.
EK27
Selected Profile
0 - No profile selected.
1 - Gas profile 1.
2 - Oil profile 1.
3 - Gas profile 2.
4 - Oil profile 2.
EK28
Setpoints Entered
The number of fuel/air setpoints entered for the current profile, where:
0 - No setpoints entered.
1 - Close setpoint only.
2 - Close and purge setpoints.
3 - Close, purge and ignition.
4 - Close, purge, ignition and low fire.
5 thru 24 -etc.
EK29
Commission Status
Current commissioning mode, where:
0 - Normal run mode.
1 - Adjust ratio mode.
2 - Commission ratio mode.
EK30
Commission Profile
The expected commission ratio profile, where:
1 - Gas profile 1.
2 - Oil profile 1.
3 - Gas profile 2.
4 - Oil profile 2.
EK31
Commission Setpoint
The current commission ratio setpoints:
0 - Closed setpoint.
1 - Purge setpoint.
2 - Ignition setpoint.
3 - Low fire setpoint.
4 thru 24 - profile setpoints
EK32
Number of Commission Setpoints
The number of setpoints entered in the current commission ratio session:
0 - No setpoints entered.
1 - Close setpoint only.
2 - Close and purge setpoints.
3 - Close, purge and ignition.
4 thru 24 - profile setpoints.
EK33
Modulation Mode
The current modulation mode:
0 - Auto mode.
1 - Manual from external limit.
2 - Manual from keyboard.
3 - Boiler sequencing control.
4 - Low fire hold.
EK34
Undefined
EK35
Shutdown profile setpoint
When the unit performs a safety shutdown, this shows the number of the
profile setpoint nearest to the last modulation position.
EK36
Flame Sensor Signal Value
Signal value received from the flame sensor input.
A steady signal of 10 or greater is required for reliable operation.
EK37
Measured Gas Pressure (mBar)
Measured pressure from gas pressure sensor (sensor must be enabled and
gas must be selected).