72
£
OPTION
DESCRIPTION
VALUES
ALLOWABLE VALUES
10.9
I/P 5 function
Air
Pressure
Switch 2
Flow
0- Air Pressure Switch 2 NO FLOW
1- Auto/Manual selection
2- Manual Up
3- Manual Down
4- Setpoint select
5- Release to ignite
6- Release to modulate.
7- Lead boiler select.
8- Profile select
9- Purge Hold (Switch close hold purge).
10- Oil valve proof of closure.
11- Gas valve proof of closure.
12- Trim Enable
11.0
Relay Output Enable
0 - Disabled
1 - Relay Output Enabled
OPTION
DESCRIPTION
VALUES
ALLOWABLE VALUES
11.9
Alarm 2 Output
0 -No Selection
1- Motor Related Fault
2- FAult Causing Non-Volitale Lockout
3- External Shutdown Condition
4- External Alarm Condition
5- Flame Failure
6- Valve Proving.
7- Air Pressure
8- Burner Modulating
9- Burner Control Value Exceeded
10- Safety Limit Exceeded
11- Burner at Low Fire Hold
12- Burner in Manual Control
13 - Burner in PID or Tracking Modulation Control
14 - Fuel 1 Selected
15 - Fuel 2 Selected
16 - Burner Under Sequence Control
17 - Burner is selected as lead under sequence control
18 - Gas Pressure
20 -Modulation Rate
12.0
Lead Lag Enable
0- Disabled. The unit operates in a stand-alone mode.
1- Enabled. The unit will modulate and sequence its boiler
according to instructions received from the lead boiler. If
communication with the lead boiler is lost, the unit oper-
ates in stand-alone mode.
12.1
LL Priority
0-9
Lead, 1, 2, 3, 4, 5, 6, 7, 8, 9,
Lead, 6, 7, 8, 9, 0, 1, 2, 3, 4,
12.2
Low Fire Burner Output
0.0-99.9 MW
12.3
High Fire Burner Output
0.0-99.9 MW
12.4
Lead Boiler Select
0- Not Lead
1- Lead boiler
12.5
Standby Low Limit Control Value
0-999
12.6
Standby High Limit Control Value
0-999
COMMISSIONING SHEET