73
®
OPTION
DESCRIPTION
VALUES
ALLOWABLE VALUES
12.7
Sequencing Up Delay
1-15 minutes
12.8
Sequencing Down Delay
1-15 minutes
13.1
Sustain Mod Hi
0-15 minutes
13.2
Sustain Mod Low
0-15 minutes
14.0
Inverter/ Auxiliary Damper enable
0- Disabled
1- Enabled
14.1
Inverter/ Auxiliary Damper enable Profile 1
0- Inverter speed control disabled
1- Inverter speed control enabled for relevant fuel/profile.
2- Auxiliary damper control enabled for relevant fuel/pro-
file.
3- Inverter and auxiliary damper enabled for relevant fuel/
profile.
14.2
Inverter/ Auxiliary Damper enable. Profile 2
0- Inverter speed control disabled.
1- Inverter speed control enabled for relevant fuel/profile.
0- Auxiliary damper control enabled for relevant fuel/pro-
file.
1- Inverter and auxiliary damper enabled for relevant fuel/
profile.
14.3
Inverter/ Auxiliary Damper enable. Profile 3
0- Inverter speed control disabled.
1- Inverter speed control enabled for relevant fuel/profile.
2- Auxiliary damper control enabled for relevant fuel/pro-
file.
3- Inverter and auxiliary damper enabled for relevant fuel/
profile.
14.4
Inverter/ Auxiliary Damper enable. Profile 4
0- Inverter speed control disabled.
1- Inverter speed control enabled for relevant fuel/profile.
2- Auxiliary damper control enabled for relevant fuel/pro-
file.
3- Inverter and auxiliary damper enabled for relevant fuel/
profile.
14.5
Inverter Control Accuracy
0- Low accuracy (normal setting).
1- High accuracy (not recommend)
14.6
Inverter Error Tolerance
0- Small Tolerance (normal setting).
1- Large Tolerance
14.7
Inverter closed loop Gain
15-125%
14.8
Inverter speed stop time
0-100 seconds
20.0
Oxygen Probe select
0- No probe selected
1- Fireye Oxygen probe w/o pre-purge test.
2- Fireye Oxygen probe w/ pre-purge test
20.1
Oxygen probe calibration offset value
0-999
20.1
Oxygen probe calibration offset value
0-999
20.2
Oxygen probe calibration gain value
0-999
20.3
Oxygen probe calibration gas concentration
0-9.99%
20.4
Temperature Unit
0- °C
1- °F
COMMISSIONING SHEET