51
®
Option 13.1 - Sustained modulation time before OFF/ON transition
This parameter is an optional time delay, which is applied when the normal modulation limit for a
slave to be activated is reached. Once the time limits specified in option parameters 12.7 & 12.8
have passed (or always, in the case of a two boiler system), the modulation from the PID control is
monitored. Providing the modulation stays above the “ON” threshold for greater than the time set by
option 13.1the slave will come on.
Option 13.2 - Sustained modulation time before ON/OFF transition
This parameter is an optional time delay, which is applied when the normal modulation limit for a
slave to be de-activated is reached. Once the time limits specified in option parameters 12.7 & 12.8
have passed (or always, in the case of a two boiler system), the modulation from the PID control is
monitored. Providing the modulation stays below the “OFF” threshold for greater than the time set
by option 13.2, the slave will go “OFF”.
Options 14 thru 43 refer to Expansion Module functions. Refer to bulletin NEX-1002 for
explanations/Details regarding these option parameters.
Option 50.0 - Erase enable (0 - 1)*
CAUTION: If this value is displayed as a “2” the option parameter data has been up-loaded
into the unit, ensure all option parameters are set to match the requirements of the burner it
is connected to. Failure to do so could cause a hazardous condition to occur. After all option
parameters have been checked to match the requirements of the burner it is connected to,
reset this option parameter to zero to allow the system to operate. If an attempt is made to
operate the system, with this option parameter set to “2” a fault will be generated and the
unit will perform a safety shutdown, preventing the burner from firing.
In order to erase information in memory for a specific profile selection, this option must be set to
“1”. Once the unit has left setup mode, this parameter will automatically be reset to “0”.
If this option parameter is set to “2” see caution message above.
Option 50.1 - Erase command (0 - 5)*
When erase enable (option 15.0) is set to “1”, this option parameter determines which information
will be erased when the unit leaves option set mode.
If
5
is selected,
all profile setpoints will be erased and all option parameters will be set to
default values.
The unit will be initialized to the same state as when it was shipped.
0
No erase
1
Erase gas profile 1 (profile 1)
2
Erase oil profile 1 (profile 2)
3
Erase gas profile 2 (profile 3)
4
Erase oil profile 2 (profile 4)
5
Erase all setpoints and initialize all option parameters