69
®
OPTION
DESCRIPTION
VALUES
ALLOWABLE VALUES
5.9
Modulation Switch
0-99%
6.0
Setpoint 1 Input Type
0- Track modulation input. (Where minimum input signal=
low fire, Maximum input signal= high fire)
1- Measure value input, PID XXX control, values displayed
with no decimal place
2- Measure value input, PID XX.X control, values displayed
with 1 decimal place.
3- Measure value input, PID X.XX control, values displayed
with 2 decimal places.
6.1
Setpoint Zero Value
0-999
6.2
Setpoint 1 Span Value
0-999
6.3
Setpoint control Value
0-999
6.4
Setpoint 1 Proportional Band
0-999
6.5
Setpoint 1 Integral Term
0-999
6.6
Setpoint 1 Derivative Term
0-999
6.7
Setpoint 1 Remote Zero Value
0-999
6.8
Setpoint 1 Remote Span Value
0-999
7.0
Setpoint 1 Control Limit Type
0- No limits
1- Absolute limit. The values entered in the option parame-
ters 7.1 and 7.2 are the actual limit values.
2- Deviation limit. The values entered in option parameters
7.1 and 7.2 represent a deviation from the setpoint 1 con-
trol value. This means that if the setpoint control value is
changed, the limits are automatically changed correspond-
ingly.
7.1
Setpoint 1 Low Limit Control Value
0-999
7.2
Setpoint 1 High Limit Control Valve
0-999
7.5
Setpoint 1 Warming Limit
0-999
7.6
Setpoint 1 Warming Time
0-360
8.0
Setpoint 2 Input Type
0- Not used.
1- Track modulation input. (Where minimum input signal =
low fire, maximum input signal = high fire.
2- Measure value input, PID XXX control, values displayed
with no decimal place.
3- Measure value input, PID XX.X control, values displayed
with 1 decimal place.
4- Measure value input, PID X.XX control, values displayed
with 2 decimal places.
8.1
Setpoint 2 Zero Value
0-999
8.2
Setpoint 2 Span Value
0-999
8.3
Setpoint 2 Control Valve
0-999
8.4
Setpoint Proportional Band
0-999
8.5
Setpoint 2 Integral Term
0-100
8.6
Setpoint 2 Derivative Term
0-100
COMMISSIONING SHEET