4
£
Technical Specifications
General
Supply Voltage:
120/230 VAC
Power Consumption:
Approx. 20VA
Supply Frequency:
50/60Hz
Ambient Temperature Range:
32 -140°F (0 to 60°C)
Maximum Connected Load:
2000 VA
Control Unit Protection Category:
NEMA 1 (IP 00) The unit must be situated in a clean
environment according to EN 6730-1.
Indoor: Unit must be mounted in a NEMA 12, IP52
rated enclosure
Outdoor: Unit must be mounted in a NEMA 4, IP
rated enclosure
Unit Dimensions:
Wiring Base, UL listed:
6 7/32" (158mm)W x 13.0" (330mm)H
Wiring Base, UL Recognized:
6 1/8" (155.2mm)W x 11 1/16" (280mm)H
Control unit:
3.0" (78mm)W x 9.0” (225mm)H x 5 7/8" (148mm)D
5 7/8" (148 mm) tall, installed in wiring base
Weight:
6.6 lbs (3.0kg) including wiring base
Type of Display:
2 line 20 character dot-matrix vacuum fluorescent
Servo-Motor Control
Type:
AC up/down with feedback potentiometer.
Maximum Number of Servo-Motors: 3 Channel = 2 Fuel, 1 Air
4 Channel = 2 Fuel, 2 Air
Maximum Number of Fuels/Profiles: 2/4
Max. Number of Setpoints Per Profile24 including close, purge and ignition
Positioning Accuracy: 0.1°
Response Time to Positioning Error: 15s for +/- 1.0°, 1s for +/- 5.0°
Maximum Motor Current:
150mA rms
Maximum Motor Voltage:
250VAC rms
Motor Speed Range:
10s/90° to 60s/90°
Potentiometer Feedback Voltage:
+ 5Vdc for potentiometer with full range travel
+15Vdc for 340° potentiometer with 90° travel
(selected using a link).
Potentiometer Resistance Range: 1 to 5K ohms @ 5V
3 to 15K ohms @15V
Relay Outputs
Alarms
Type:
On-off relay, de-energize for off.
Maximum Current:
2A rms (pilot duty) / 4A rms (power factor > 0.6)
Maximum Voltage:
250VAC rms