29
®
CONTROL LED INDICATORS
The control unit display is comprised of one red (fault) indicator and seven green (operational) indi-
cators.
During normal operation, the red indicator is off and the seven green indicators show status informa-
tion (see below).
If a fault occurs, the red indicator is illuminated and the green indicators show the fault number (see
Fault Listing).
HOURS RUN
Displays the hours run for the current profile selection. If no profile is selected, the display will show ‘---’.
P n
A n
This display parameter is used in commission ratio.
This display is used in adjust ratio mode.
They indicate the profile setpoint currently under adjustment or being displayed. If the display is flashing, the unit is waiting for an
event to occur before the point may be altered. When the display stops flashing, the point may be altered. PROFILE SET is not
available in run mode.
MODULATION
This is the percentage modulation rate based on the position of the lead drive, where 0% is low fire and 100% is high fire.
GAS PRESSURE
Measured gas pressure in mBar. This parameter is only available if the gas pressure sensor input is enabled (see section on Option
Paramenters for details).
FLAME SIGNAL
0 - 100 display of flame signal, values above 5 are taken as flame present. A signal of 10 should be maintained for normal burner
operation
AUTO
Flashed when the unit is in sequencing mode.
Illuminated when unit is in auto modulation mode.
STATUS
Illuminated when boiler pressure/temperature is below the low control
limit and the burner is ready to fire.
PURGE
Flashed when the servo-motors are moving to pre-purge.
Illuminated during the pre-purge time.
IGNITION
Flashed when the servo-motors are moving to ignition.
Illuminated when the burner is in ignition sequence.
RUN
Flashed when the servo-motors are moving from ignition to low fire.
Illuminated when the burner is in ignition sequence.
FLAME
Illuminated when a flame signal is detected.
AIR
Illuminated when air pressure is detected by the air pressure switch.
FAULT INDICATOR
Illuminated when a fault causes safety shutdown.
A
B
C
D
E
F
G