58
£
F66
Drive selection fault
Selected profile requires drive which is not available, check option parameters
1.3, 14.x .
L67
Aux 1 Limit
The 4-20mA auxiliary input signal is above the limit set by the corresponding
option parameter.
Its value is displayed on EK 87.
L68
Aux 2 Limit
The 4-20mA auxiliary input signal is above the limit set by the corresponding
option parameter.
Its value is displayed on EK 88.
L69
Aux 3 Limit
The 4-20mA auxiliary input signal is above the limit set by the corresponding
option parameter.
Its value is displayed on EK 89.
L70
Aux 4 Limit
The 4-20mA auxiliary input signal is above the limit set by the corresponding
option parameter.
Its value is displayed on EK 90.
F76
Secondary flame sen-
sor input fault
The flame sensor input is not responding correctly. If the fault persists for 23
hours, the burner will be shutdown.
F77
Secondary non-vola-
tile lock-out relay fault
A secondary fault has occurred with the main 1, main 2, pilot, vent or non-vol-
atile lock-out relays. If the fault persists for 23 hours, the burner will shut-
down.
Subset: +1 - non-volatile lockout, =2 - main1, =4 - main2, =8 -pilot, =16 -vent.
F78
Secondary program
memory checksum
fault
A fault has occurred with the program memory on the CPU board. If the fault
persists for 23 hours, the burner will shutdown.
• Contact supplier.
F79
Secondary watchdog
fault
A fault has occurred with the CPU watchdog. If the fault persists for 23 hours,
the burner will shutdown.
• Contact supplier.
NO
LED
A B C D E F G
NAME
DESCRIPTION