71
®
OPTION
DESCRIPTION
VALUES
ALLOWABLE VALUES
10.3
I/P C Function
Same as 10.1
10.4
I/P D Function
Same as 10.1
10.5
I/P F Function
Same as 10.1
10.6
I/P 2 Function
Gas Select
0- Gas Selected
1- Auto/Manual selection
2- Manual Up
3- Manual Down
4- Setpoint select
5- Release to ignite
6- Release to modulate.
7- Lead boiler select.
8- Profile select
9- Purge Hold (Switch close hold purge).
10- Oil valve proof of closure.
11- Gas valve proof of closure.
12- Trim Enable
OPTION
DESCRIPTION
VALUES
ALLOWABLE VALUES
10.7
I/P 3 Function
Oil Select
0- Oil Selected
1- Auto/Manual selection
2- Manual Up
3- Manual Down
4- Setpoint select
5- Release to ignite
6- Release to modulate.
7- Lead boiler select.
8- Profile select
9- Purge Hold (Switch close hold purge).
10- Oil valve proof of closure.
11- Gas valve proof of closure.
12- Trim Enable
10.8
I/P 4 function
Air
Pressure
Switch 2
Flow
0- Air Pressure Switch 2 FLOW
1- Auto/Manual selection
2- Manual Up
3- Manual Down
4- Setpoint select
5- Release to ignite
6- Release to modulate.
7- Lead boiler select.
8- Profile select
9- Purge Hold (Switch close hold purge).
10- Oil valve proof of closure.
11- Gas valve proof of closure.
12- Trim Enable
COMMISSIONING SHEET