Master Programming Level
Programming
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
77
3.5.7.7 ANN-RLY Options
Pressing
1
for
ANN-RLY Options
while viewing ANN-BUS Screen #3 will cause the following
screen to be displayed:
The ANN-RLY module provides ten Form-C relays which can be programmed for various
functions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will
display the remaining relays for this module.
To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option
screen, press the number key corresponding to the relay to be programmed. Following is a list
of the available programming options for each relay:
•
General Alarm
•
General Trouble
•
General Supervisory
•
Future Use
•
Future Use
•
Future Use
•
General Discharge
•
Discharge Release 1
•
Discharge Release 2
•
AC Loss
•
Waterflow Delay
•
Future Use
•
Future Use
•
Future Use
•
General 2nd Shot Release
•
2nd Shot Release 1
•
2nd Shot Release 2
•
Input Zone 1
•
Input Zone 2
•
Input Zone 3
•
Input Zone 4
•
Input Zone 5
•
Input Zone 6
PROGRAMMING
1=ANN-RLY OPTIONS
2=ANN-LED OPTIONS
ANN-BUS Screen #3
ANN-RLY OPTIONS
1=RELAY 1 IN ZONE 1
2=RELAY 2 IN ZONE 2
3=RELAY 3 IN ZONE 3
ANN-RLY Options Screen
Содержание MRP-2001
Страница 8: ...Notes 8 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 19: ...Backbox Mounting Installation MRP 2001 MRP 2001E PN 53040 A 4 16 2007 19 Figure 2 3 Backbox 9050udcab cdr ...
Страница 126: ...Testing Maintenance Maintenance 126 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 132: ...Testing Maintenance Maintenance 132 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 133: ...Maintenance Testing Maintenance MRP 2001 MRP 2001E PN 53040 A 4 16 2007 133 ...
Страница 134: ...Testing Maintenance Maintenance 134 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 136: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...