Installation
Output Circuits
24
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
2.4.2 Special Application DC Power Output Connections
Special Application Resettable and Nonresettable 24 VDC power is available on the MRP-2001
control panel.
2.4.3 Relays - Programmable
The MRP-2001control panel provides a factory default programmed alarm relay, fail-safe trouble
relay and supervisory relay. Each relay can be programmed to activate for other conditions (refer
to "On-Board Relays" on page 64). Each Form-C relay is rated for 2 amps @ 30VDC (resistive)
and 0.5 amps @ 30 VAC (resistive).
Note that relay connections must be power-limited.
Figure 2.8 Special Application Auxiliary Power
Special Application
4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, resettable power for 4-wire smoke detectors
can be obtained from these terminals (power-limited)
Special Application
Resettable or Nonresettable Power (500 mA)
24 VDC filtered, resettable or nonresettable power can be
obtained from these terminals (power-limited)
•
Jumper JP31 pins 1 & 2 for nonresettable power (as
illustrated in figure to right)
•
Jumper JP31 pins 2 & 3 for resettable power
-
+
-
+
ms-10UDtb9.cdr
4
3
2
1
Figure 2.9 Relay Terminals
Note
: Relay contacts are shown with
power applied to the panel and no active
troubles, alarms or supervisories.
The Trouble Relay is a fail-safe relay
which will transfer on any trouble or
total power failure.
m
s10udre
la
y.cdr
Содержание MRP-2001
Страница 8: ...Notes 8 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 19: ...Backbox Mounting Installation MRP 2001 MRP 2001E PN 53040 A 4 16 2007 19 Figure 2 3 Backbox 9050udcab cdr ...
Страница 126: ...Testing Maintenance Maintenance 126 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 132: ...Testing Maintenance Maintenance 132 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 133: ...Maintenance Testing Maintenance MRP 2001 MRP 2001E PN 53040 A 4 16 2007 133 ...
Страница 134: ...Testing Maintenance Maintenance 134 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 136: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...