Circuit Mapping and Cross-Zoning
Input-to-Output Circuit Mapping and Cross-Zone Operation
104
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
A.1.1 Mapping Input Zones to Output Circuits for Direct Activation
Using the INPUT ZONES menus, you can assign any input zone to directly activate (without cross-
zoning) any of the four output circuits provided they are assigned matching operational types (see
the OUTPUT CIRCUIT MAP menu within the INPUT ZONES menus).
Example 1:
A waterflow input zone assigned to directly activate an alarm output circuit by setting
the OUTPUT CIRCUIT MAP assignment to
YES
.
•
Output Circuit 1 is programmed as alarm NAC using the
OUTPUT CIRCUITS
menus.
•
Output Circuit 2 is programmed as Release Circuit 1 using the
OUTPUT CIRCUITS
menus.
•
Output Circuit 3 is programmed as Release Circuit 2 using the
OUTPUT CIRCUITS
menus.
•
Output Circuit 4 is programmed as supervisory NAC using the
OUTPUT CIRCUITS
menus.
•
Input Zone 1 is programmed as a waterflow zone using the INPUT ZONES menus.
Waterflow Input Zone 1 will directly activate Output Circuit 1 (Alarm NAC) but not Output
Circuits 2, 3 or 4.
Example 2:
A single hazard application where a smoke detector input zone will directly activate
both an alarm NAC circuit and a releasing output circuit.
•
Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.
•
Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.
•
Output Circuit 3 is programmed as waterflow NAC using the OUTPUT CIRCUITS menus.
•
Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.
•
Input Zone 1 is programmed as a smoke detector zone using the INPUT ZONES menus.
Smoke detector Input Zone 1 will directly activate Output Circuits 1 (Alarm NAC) and 2 (Release
1) but not output circuits 3 or 4.
ZONE 1 TYPE
1=N/A
2=WATERFLOW
3=WATERFLOW NS
OUTPUT MAP ZONE 1
1=ALARM NAC YES
2=RELEASE 1 NO
3=RELEASE 2 NO
OUTPUT MAP ZONE 1
1=SUPV BELL NAC N/A
ZONE 1 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
OUTPUT MAP ZONE 1
1=ALARM NAC YES
2=RELEASE 1 YES
3=WATERFLOW NAC NO
OUTPUT MAP ZONE 1
1=SUPV BELL NAC N/A
Содержание MRP-2001
Страница 8: ...Notes 8 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 19: ...Backbox Mounting Installation MRP 2001 MRP 2001E PN 53040 A 4 16 2007 19 Figure 2 3 Backbox 9050udcab cdr ...
Страница 126: ...Testing Maintenance Maintenance 126 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 132: ...Testing Maintenance Maintenance 132 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 133: ...Maintenance Testing Maintenance MRP 2001 MRP 2001E PN 53040 A 4 16 2007 133 ...
Страница 134: ...Testing Maintenance Maintenance 134 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 136: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...