Master Programming Level
Programming
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
59
3.5.3.2.2 Release Stage NAC
If Release Stage NAC is selected as the Output Type, the following subscreen will be displayed:
An NAC can be used to signal the two stages of a release operation. This screen allows the
programmer to select the NAC output that will indicate the release stages for Release Circuit 1
or Release Circuit 2. For a description of this feature, refer to "Release Stages" on page 91.
3.5.3.3 Silence
Pressing
1
while viewing Output Screen #2 will cause the following screen to be displayed:
Pressing
1
while viewing the Silenceable Screen will program the selected Output as a
silenceable circuit. This will allow the Output to be silenced by pressing the Alarm Silence key
or by the Auto Silence feature.
Pressing
2
while viewing the Silenceable Screen will program the selected Output as a
nonsilenceable circuit. This will prevent the selected main circuit board Output from being
silenced by pressing the Alarm Silence key or by the Auto Silence feature.
Pressing
3
while viewing the Silenceable Screen will program the selected Output as a
synchronized mute circuit. Refer to "Synchronized NAC Operation" on page 62 for a
description of synchronization.
Note: If the Output Circuit has been programmed as a Releasing Circuit, the Silenceable
Option will not be available and the display will indicate
N/A
next to it.
Important: When an Output Circuit with a mix of audible and visual devices is programmed for
Sync Mute, only the audible devices will be turned off if the Silence key is pressed or if the
Autosilence feature is enabled. The visual devices (strobes, etc.) will continue to operate.
RELEASE STAGES
1=RELEASE 1 ONLY
2=RELEASE 2 ONLY
OUTPUT #
1=SILENCE NON-SIL
2=AUTO SILENCE NO
3=SIL INHIBITED NO
Output Screen #2
SILENCEABLE
1=SILENCEABLE
2=NON SILENCEABLE
3=SYNC MUTE
Silenceable Screen
Содержание MRP-2001
Страница 8: ...Notes 8 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 19: ...Backbox Mounting Installation MRP 2001 MRP 2001E PN 53040 A 4 16 2007 19 Figure 2 3 Backbox 9050udcab cdr ...
Страница 126: ...Testing Maintenance Maintenance 126 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 132: ...Testing Maintenance Maintenance 132 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 133: ...Maintenance Testing Maintenance MRP 2001 MRP 2001E PN 53040 A 4 16 2007 133 ...
Страница 134: ...Testing Maintenance Maintenance 134 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 136: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...