Maintenance
Testing & Maintenance
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
125
Test i
3
Series detectors as follows:
Test Switch
1. An opening for the recessed test switch is located on the detector housing.
2. Insert a small screwdriver or allen wrench (0.18” max.) into the test switch opening; push
and hold.
3. If the detector is within the listed sensitivity limits, the detector’s red LED should light
within five seconds.
Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow the smoke
through the detector until it alarms.
Note: For the above tests, the detector will reset only after the power source has been momentarily
interrupted.
If a detector fails any of the above test methods, its wiring should be checked and it should be
cleaned as outlined in the Maintenance section of the System Sensor Document. If the detector still
fails, it should be replaced.
Notify the proper authorities when the system is back in service.
E.2 Maintenance
A regular schedule of inspection, testing and maintenance is vital to ensure proper and reliable
operation of the control panel. The procedures should be performed as required by the local
authority having jurisdiction. Refer to NFPA documentation for further details.
Содержание MRP-2001
Страница 8: ...Notes 8 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 19: ...Backbox Mounting Installation MRP 2001 MRP 2001E PN 53040 A 4 16 2007 19 Figure 2 3 Backbox 9050udcab cdr ...
Страница 126: ...Testing Maintenance Maintenance 126 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 132: ...Testing Maintenance Maintenance 132 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 133: ...Maintenance Testing Maintenance MRP 2001 MRP 2001E PN 53040 A 4 16 2007 133 ...
Страница 134: ...Testing Maintenance Maintenance 134 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 136: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...