Master Programming Level
Programming
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
57
3.5.3 Output Circuits
The options for the Output Circuits on the control panel main circuit board can be configured by
pressing
2
while viewing Programming Screen #2. The following screens will be displayed:
The Output Circuits can be configured independently by pressing
1
for Output 1,
2
for Output 2,
3
for Output 3 or
4
for Output 4.
To program an Output circuit, press the number corresponding to the Output to be programmed.
The following screens will be displayed for each selection:
PROGRAMMING
1=FACP CONFIG
2=INPUT ZONES
3=OUTPUT CIRCUITS
Programming Screen #1
OUTPUT CIRCUITS
1=OUTPUT 1
2=OUTPUT 2
3=OUTPUT 3
NAC Selection Screen
OUTPUT CIRCUITS
1=OUTPUT 4
NAC Selection Screen
OUTPUT #
1=ENABLED YES
2=TYPE ALARM NAC
Output Screen #1
Output Screen #2
OUTPUT #
1=SILENCE NON-SIL
2=AUTO SILENCE NO
3=SIL INHIBIT NO
Output Screen #3
OUTPUT #
1=CODING
STEADY
Содержание MRP-2001
Страница 8: ...Notes 8 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 19: ...Backbox Mounting Installation MRP 2001 MRP 2001E PN 53040 A 4 16 2007 19 Figure 2 3 Backbox 9050udcab cdr ...
Страница 126: ...Testing Maintenance Maintenance 126 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 132: ...Testing Maintenance Maintenance 132 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 133: ...Maintenance Testing Maintenance MRP 2001 MRP 2001E PN 53040 A 4 16 2007 133 ...
Страница 134: ...Testing Maintenance Maintenance 134 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 136: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...