Master Programming Level
Programming
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
79
3.5.9 Walktest
Walktest allows an individual to test the fire alarm system without the necessity to reset the control
panel after each device activation. Pressing
3
while viewing the Programming Screen #3 will cause
the following Walktest options to be displayed:
To perform a silent walktest which will not sound the NACs, press
1
while viewing the Walktest
Screen. To perform an audible walktest, which will sound the NACs, press
2
while viewing the
Walktest Screen. When either option is chosen, the panel will enter Walktest Mode and the
following screen will be displayed:
The user can now perform a one-person walktest by activating devices throughout the system. As
each device is activated, the screen will display the information about the activated device as shown
below. Note that the
colon (:)
in the time is replaced with an
asterisk (*)
to distinguish the
walktest screen from an actual alarm screen.
After completion of the Walktest, press the
Esc
(Escape) key to exit Walktest Mode and return to
the Walktest Screen. The results of the Walktest can now be viewed by pressing
3
while viewing
the Walktest Screen. The following screen will be displayed:
Use the up and down arrow keys to view all of the walktest results which will be displayed as
illustrated in the preceding screen. Note that the Walktest log is stored in RAM. If all power (AC
and DC) is removed from the FACP, the Walktest log information will be lost. This information is
also overwritten when subsequent walktests are performed.
PROGRAMMING
1=ANN-BUS
2=HISTORY
3=WALKTEST
Programming Screen #3
WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW EVENTS
Walktest Screen
UNIT IN WALKTEST
Walktest Active Screen
ALARM ZONE 1
<ADJ> <NOUN>
Z01
10*00A 010805
WALKTEST EVENTS
Содержание MRP-2001
Страница 8: ...Notes 8 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 19: ...Backbox Mounting Installation MRP 2001 MRP 2001E PN 53040 A 4 16 2007 19 Figure 2 3 Backbox 9050udcab cdr ...
Страница 126: ...Testing Maintenance Maintenance 126 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 132: ...Testing Maintenance Maintenance 132 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 133: ...Maintenance Testing Maintenance MRP 2001 MRP 2001E PN 53040 A 4 16 2007 133 ...
Страница 134: ...Testing Maintenance Maintenance 134 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 136: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...