Template 11: Single Hazard - 3 Zones and Low Pressure
FACP Configuration Templates
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
113
B.5 Template 11: Single Hazard - 3 Zones and Low Pressure
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding
output circuit).
Input Zone Types:
•
Zone 1 = 2-wire smoke
•
Zone 2 = Fire
•
Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
•
Zone 4 = Manual Release
•
Zone 5 = Pull Station
•
Zone 6 = Low Pressure
Output Circuit Types:
•
Output 1 = Alarm NAC
•
Output 2 = Waterflow NAC - activation delayed for 10 secs. (Waterflow Delay set to10 secs.)
•
Output 3 = Supervisory Bell NAC
•
Output 4 = Release Solenoid 1 (unsupervised for shorts)
Timers
•
Soak Timer 1 - set for 10 minutes
•
Soak Timer 2 - set for 10 minutes
•
Waterflow Delay Timer - set for 10 seconds
•
AC Loss Delay Timer - set for 2 hours
Operation
•
Activation of Input Zone 1 (2-Wire Smoke)
or
Zone 2 (Fire)
or
Zone 4 (Manual Release)
or
Zone 5 (Pull Station) will operate the Alarm NAC Output #1 and Release Solenoid 1 Output
#4. Release Solenoid 1 will turn off water release following time-out of the 10 minute Soak
Timer 1
•
Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is
a 10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10
seconds
•
Activation of Input Zone 6 (Low Pressure) will operate the Supervisory Bell NAC Output #3
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
•
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull
Station) will operate Alarm Relay
•
Trouble Relay - any system trouble will activate the Trouble Relay
•
Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay
TEMPLATE 11: SINGLE HAZARD - 3 ZONES AND LOW PRESSURE
INPUT ZONES
1
2
3
4
5
6
OUTPUT CIRCUITS
2-WIRE SMOKE
FIRE
WATERFLOW
MANUAL
RELEASE
PULL
STATION
LOW
PRESS.
#1 ALARM NAC
X
X
X
X
#2 WATERFLOW NAC
X
#3 SUPV. BELL NAC
X
#4 RELEASE SOLENOID 1
X
X
X
X
Содержание MRP-2001
Страница 8: ...Notes 8 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 19: ...Backbox Mounting Installation MRP 2001 MRP 2001E PN 53040 A 4 16 2007 19 Figure 2 3 Backbox 9050udcab cdr ...
Страница 126: ...Testing Maintenance Maintenance 126 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 132: ...Testing Maintenance Maintenance 132 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 133: ...Maintenance Testing Maintenance MRP 2001 MRP 2001E PN 53040 A 4 16 2007 133 ...
Страница 134: ...Testing Maintenance Maintenance 134 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 136: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...