![Fire-Lite Alarms MRP-2001 Скачать руководство пользователя страница 60](http://html.mh-extra.com/html/fire-lite-alarms/mrp-2001/mrp-2001_installation-operation-and-programming-manual_2291117060.webp)
Programming
Master Programming Level
60
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
3.5.3.4 Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit board
silenceable notification appliances after a programmed length of time. To enable this feature
and program the time delay before Auto Silence activation, press
2
while viewing Output
Screen #2. The following screens will be displayed:
To disable the Auto Silence feature, press
1
for
No
while viewing Auto Silence Screen #1. To
enable the Auto Silence feature, press the number corresponding to the time delay which will
elapse before Auto Silence activates. This information will be stored in memory and the
display will return to NAC Screen #1.
Note: If the Output Circuit has been programmed as a Releasing Circuit, the Auto Silence
Option will not be available and the display will indicate
N/A
next to it.
3.5.3.5 Silence Inhibited
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit
board Output for a period of one minute. Resetting the FACP will also be prevented for one
minute while the Output programmed for silence inhibit is activated. Pressing
3
while viewing
Output Screen #2 will cause a screen to be displayed with the options
1=No Silence Inhibit
and
2=1 Min. Silence Inhibit
. Pressing
1
will disable the Silence Inhibit feature while pressing
2
will enable a 1 minute Silence Inhibit for the selected Output.
AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
Auto Silence Screen #1
AUTO SILENCE
1=30 MINUTES
Auto Silence Screen #2
AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #3
OUTPUT #
1=SILENCEABLE YES
2=AUTO SILENCE NO
3=SIL INHIBITED NO
Output Screen #2
Содержание MRP-2001
Страница 8: ...Notes 8 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 19: ...Backbox Mounting Installation MRP 2001 MRP 2001E PN 53040 A 4 16 2007 19 Figure 2 3 Backbox 9050udcab cdr ...
Страница 126: ...Testing Maintenance Maintenance 126 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 132: ...Testing Maintenance Maintenance 132 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 133: ...Maintenance Testing Maintenance MRP 2001 MRP 2001E PN 53040 A 4 16 2007 133 ...
Страница 134: ...Testing Maintenance Maintenance 134 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 136: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...