Input-to-Output Circuit Mapping and Cross-Zone Operation
Circuit Mapping and Cross-Zoning
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
103
APPENDIX A
Circuit Mapping and Cross-Zoning
A.1 Input-to-Output Circuit Mapping and Cross-Zone Operation
The flexible cross-zoning and input-to-output (I/O) mapping capability of this fire panel provides a
powerful toolset to accommodate many site-specific configurations. To simplify initial setup,
preconfigured application templates that employ cross-zoning and I/O mapping are included from
the factory. Refer to "FACP Configuration Templates" on page 108 for a description of each
supplied template.
The following sections provide some examples of setting up your own cross-zoned or I/O mapped
system.
The Installer is responsible for completely testing the proper operation of the fire panel as set
up by programming.
Notes:
1. Any general system trouble, such as a battery fault, will activate any output circuit
programmed as
TROUBLE NAC
in the
OUTPUT CIRCUITS
menu. Circuit mapping does
not apply.
2. Any input zone programmed for supervisory operation or as a
DISABLE RELEASE
switch in
the
INPUT CIRCUITS
menus will activate any output circuit programmed as
SUPV BELL
NAC
in the
OUTPUT CIRCUITS
menus. Circuit mapping does not apply.
3. The programming menus will prevent you from mapping any incompatible input zone and
output circuit types together, such as mapping a supervisory input zone to a releasing output
circuit.
4. Timers and/or delays are not represented in these examples.
!
Содержание MRP-2001
Страница 8: ...Notes 8 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 19: ...Backbox Mounting Installation MRP 2001 MRP 2001E PN 53040 A 4 16 2007 19 Figure 2 3 Backbox 9050udcab cdr ...
Страница 126: ...Testing Maintenance Maintenance 126 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 132: ...Testing Maintenance Maintenance 132 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 133: ...Maintenance Testing Maintenance MRP 2001 MRP 2001E PN 53040 A 4 16 2007 133 ...
Страница 134: ...Testing Maintenance Maintenance 134 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Страница 136: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...