TWINFLEX
®
SRP Control Panel Engineering and Commissioning Manual
50
The Test Controls & Display function allows the selection of multiple
tests. Select Enter to execute the selected test.
The Test Display function causes the LCD screen to display a #
symbol in each character location to indicate each character location
is operational. Test will timeout and return to test screen or press the
Esc
key to exit the test.
The Test LEDs function causes the panel LEDs to toggle on/off and
will illuminate to ensure correct operation. When this option is active,
the test LED will flash. Test will timeout and return to test screen or
press the
Esc
key to exit the test.
The Test Buzzer function turns the buzzer on to ensure correct buzzer
operation unless the buzzer has been disabled by fitting a jumper link
to J1 on the PCB. Test will timeout and return to test screen or press
the
Esc
key to exit the test.
The Test Keypad function enables the user to select each button to
ensure the correct function is shown on the screen. Press the
Esc
key
TWICE
to exit the menu.
3
Test Modes
Test Ctrls & Disp
3
Test Modes
Test Ctrls & Disp
LCD display
3 Test Modes
Test Ctrls & Disp
LEDs
3
Test Modes
Test Ctrls & Disp
Buzzer
3 Test Modes
1 Test Ctrls & Disp
4 Keypad
#######################
LED TEST
LEDS ARE BLINKING …
(TEST ENDS IN 10 SEC)
BUZZER TEST
BUZZER IS SOUNDING …
(TEST ENDS IN 10 SEC)
KEYPAD TEST
“SILENCE ALARMS”
IS BEING PRESSED
Esc & Esc to End Test
TESTS (10 seconds):
LCD DISPLAY LEDS
BUZZER KEYPAD
→ /← /
Enter
/
Esc