TWINFLEX
®
SRP Control Panel Engineering and Commissioning Manual
52
Allows inputs
1 - 5 to be verified. Indicates status of input.
Blank = input is not configured
N
= switch is not active (see page 18)
A
= switch is active
S
= circuit is shorted
O
= circuit is open
This allows the time and date to be adjusted. Use the
LEFT
and
RIGHT
arrow keys to move the cursor between digits and the
UP
and
DOWN
arrow keys or the number keys to change values. Press the
ENTER
key to confirm the change.
The date is displayed using the format set in Set Date Format in the
Time And Date menu.
Note: If the SRP panel is powered down it will not retain the time
and date. The correct time and date will need to be re-
programmed after the panel is powered up.
This allows the date format to be set.
Formats allowed: YYYY-MM-DD, MM-DD-YYYY, DD-MM-YYYY
(default = DD-MM-YYYY)
This allows the Daylight Saving Time to be set.
DST: Allows DST to be turned on or off
MONTH: Set what month DST activates for forward or backward
DAY: Set the day of the week on which DST activates and in what
week of the month (1
st
, 2
nd
, 3
rd
, 4
th
, L (Last)).
TIME: Set what hour of the day DST activates.
Enable or Disable all Relay outputs.
Mode: Enable or Disable (default = enable)
3. Test Modes
5. Test Inputs
4 Time And Date
1 Set Time & Date
4 Time And Date
2 Set Date Format
4. Time And Date
3 DST Settings
5 Enable/ Disable
1 Relays
TEST INPUT
1 2 3 4 5
N N N N N
Esc to return
SET DATE FORMAT
STYLE: DD-MM-YYYY
↑/↓ /
→ /← /
Enter
/
Esc
DST: Off FWD BACK
MONTH: Mar Oct
DAY: Sun L Sun L
TIME: 01:00 01:00
SET TIME & DATE
TIME: 13:10
DATE: 2014/03/17
↑/↓ /
→ /← /
ENTER
/
Esc
ENABLE/DISABLE
RELAY: 01
MODE: Enable
↑/↓ /
→ /← /
Enter
/
Esc