Fire Alarm Controls
The main Fire Alarm Controls may be enabled by turning the
Enable Controls key switch to the Enabled position, or by
entering a valid access code
The Silence Alarms button will silence any fire alarm sounders
that are currently sounding.
The Reset System button will reset the panel and place the
system into a non-alarm state.
The Sound Alarms button will activate all fire alarm sounders.
The Silence Buzzer button will silence the panel buzzer if it is
currently buzzing.
The Function key will activate any Programmable Relays that
are configured to EXTRACT, if the system is in the Release
state.
System Controls
A context-driven, cursor highlighted-selection menu system is used to navigate
around the menu system, automatically prompting you with the relevant options
for your Access Level and system status.
The menus may be navigated using the system control keys. Use the
UP
/
DOWN
arrow keys to move the selection arrow to the desired option and press
ENTER
or the
RIGHT
arrow key to select the chosen one.
Press the
Esc
or the
LEFT
arrow key to exit to the previous menu.
Extinguishant Release Controls
The extinguishant release switch allows the user to manually release the extinguishing agent directly from the
control panel. To operate the switch, the user must pull down the protective cover and then push the release
button.
The auto/manual key switch allows the user to place the fire alarm system in ‘automatic’ or ‘manual’ operation
modes. When set to the default ‘automatic’ mode, the control panel will operate in a normal fashion and will
advance to release through automatic detection methods.
When set to ‘manual’, the control panel’s zone circuits will not advance the system into release. In this mode,
the only way to release the extinguishant system is to manually activate it.
MAIN MENU
1 VIEW EVENTS
2 VIEW LOGS
3 TEST MODES