TWINFLEX
®
SRP Control Panel Engineering and Commissioning Manual
49
The Event Log stores 61184 fire, fault and system events which may
be displayed in a single group or by category. These may be scrolled
through with the
LEFT
and
RIGHT
arrow keys. Press the
Esc
key to
exit the menu.
When event log storage is nearly full, a “MEMORY ALMOST FULL!”
event will occur. When event log storage has run out, the most recent
512 event logs will be erased and event logs will continue being
stored
—however, a fault condition will then exist and can only be
cleared by contacting your distributor.
The Fire Log will display a log of any fire conditions received by the
panel. These may be scrolled through with the
LEFT
and
RIGHT
arrow keys. Press the
Esc
key to exit the menu.
.
The Disable Log will display any current disables. These may be
scrolled through with the
LEFT
and
RIGHT
arrow keys. Press the
Esc
key to exit the menu.
The Fault Log will display a log of any fault conditions received by the
panel. These may be scrolled through with the
LEFT
and
RIGHT
arrow keys. Press the
Esc
key to exit the menu.
The Panel Event Log will display a log of events generated from the
panel. These may be scrolled through with the
LEFT
and
RIGHT
arrow keys. Press the
Esc
key to exit the menu.
2 View Logs
1 All Logs
2 View Logs
2 Fire Events
2 View Logs
3 Disable Events
2 View Logs
4 Fault Events
2 View Logs
5 Panel Events
FAULT 44/29563
2014/03/22 14:22:02
EARTH FAULT
→ /← /
Esc
LOG
FIRE 2/154
2014/03/22 14:22:02
ZONE 1 SMOKE ALARM
→ /← /
Esc
LOG
FAULT 853/2695
2014/03/22 14:22:02
EARTH FAULT
→ /← /
Esc
LOG
PANEL 7723/47901
2014/03/22 14:22:02
CONTROLS ENABLED
→ /← /
Esc
LOG
DISABLE 2/4
2014/03/22 14:22:02
ZONE 1 DISABLED
→ /← /
Esc
LOG