TWINFLEX
®
SRP Control Panel Engineering and Commissioning Manual
51
Test Off
– Stops all test modes.
Silent - Allows the selection of one or more detection-
zones to operate in a ‘silent one-man walk test mode’. On
triggering a device, the device LED operates and the event is recorded into the event log as a test activation,
but the sounder does not sound and the control panel does not show an alarm. After approximately 5 seconds
the system will reset the device and another may be tested. The control panel event log will indicate that a test
mode has been selected. This operation will also enable the test LED and the circuit that is in test mode.
System - Allows the entire system to operate in a simple one-man walk test mode. On triggering a device the
device LED operates and the event is recorded into the event log, all the assigned sounders operate for 10
seconds and the control panel indicates DEVICE ACTIVATED. After approximately 10 seconds, the system will
reset the device and another may be tested. The control panel event log will indicate that a test mode has been
selected. Please note that with the system test mode, only the sounders that are on the same circuit as the
device being tested will sound.
To put ALL Twinflex zones into test enter 00 for the zone number.
This operation will also enable the
TEST LED and the circuit or circuits that are in test mode.
Critical note for 00 setting: If zone circuits 01, 02, 03 or 04 are set for test mode SILENT or SYSTEM and
the user scrolls to 00 it will automatically change all zone circuits to test mode OFF.
Ensure smoke is cleared from the detectors that are being tested before a reset of the system or taking
the system out of test mode as it may result in an activation in normal mode. The Detector will blink if it
senses the presence of smoke and if the detector no longer blinks then the system can be taken out of
TEST MODE.
Conventional detection circuits are not affected by test mode and will activate normally. This will bring
the circuits that are in test mode out of test mode and the system will operate as configured for the fire
event.
Allows Relays to be activated for testing.
Relay selections : Fault Relay & Relay 1 to Relay 4.
Mode: Off or On. (Default = Off)
All modes reset to Off once Esc is pressed.
Allows Outputs to be activated for testing.
Output selections : Output 1, Output 2, Output 3 (default = Output 1)
Mode: Off, Continuous, Slow, Fast, Temporal, User1, User2, User3,
User4 (default = Off)
All modes reset to Off once Esc is pressed.
3. Test Modes
2. Test Zones
3. Test Modes
3. Activate Relays
3. Test Modes
4. Activate Outputs
ACTIVATE OUTPUTS
OUTPUT: Output 1
MODE: Off
↑/↓ /
→ /← /
Esc
TEST ZONES
ZONE: 01
MODE: Test Off
↑/↓ /
→ /← /
Esc
ACTIVATE Relays
Relay: Fault Relay
MODE: Off
↑/↓ /
→ /← /
Esc