TWINFLEX
®
SRP Control Panel Engineering and Commissioning Manual
35
Access Level 1 (Normal):
Controls Enabled LED off
At Access Level 1 (Normal), the main
Fire Alarm Controls
are disabled and the following System
Menus are all that can be accessed.
Fire Alarm Controls
will only be accessible if the key switch is
turned or the User Level password is entered.
These are described below. Note that actual display indications may differ from those shown in the grey
boxes below, depending on actual set up.
The display will show any current fire events. These may be scrolled
through with the
LEFT
and
RIGHT
arrow keys. Press the
Esc
key to
exit the menu.
The display will show any current disables. These may be scrolled
through with the
LEFT
and
RIGHT
arrow keys. Press the
Esc
key to
exit the menu.
Note: When the home screen is displayed, it will automatically
change to display any fires or faults on the system as they occur.
The display will show any current faults. These may be scrolled
through with the
LEFT
and
RIGHT
arrow keys. Press the
Esc
key to
exit the menu.
The display will show any current panel events. These may be
scrolled through with the
LEFT
and
RIGHT
arrow keys. Press the
Esc
key to exit the menu.
NORMAL
View Events
1 Fires
3 Faults
2 Disables
4 Panel
5 All Events
1
View Events
1 Fire Events
1
View Events
2
Disable Events
1
View Events
3
Fault Events
1
View Events
4
Panel Events
PANEL 10/68
2014/03/22 14:22:02
CONTROLS ENABLED
→ /← /
Esc
FIRE 1/1
2014/03/22 14:22:02
ZONE 1 SMOKE ALARM
→ /← /
Esc
DISABLE 2/4
2014/03/22 14:22:02
ZONE 1 DISABLED
→ /← /
Esc
FAULT 9/19
2014/03/22 14:22:02
EARTH FAULT
→ /← /
Esc