TWINFLEX
®
SRP Control Panel Engineering and Commissioning Manual
22
Monitored outputs can be configured to the following settings:
OUTPUT TYPE
Notification
Release
OUTPUT STATE
Off
Release
Pre-Release
Alarm
OUTPUT PATTERN
Continuous
Slow
Fast
Temporal
User 1-4
SILENCEABLE
Yes
No
IMPORTANT NOTE: If the Behaviour of the monitored output is configured and then the Type is changed from
Notification to Releasing or vice versa the panel clears out the Behaviour to default setting.
Default Behaviour is OFF State, Continuous Pattern and Silenceable Output.
A Notification Output can be configured for a user defined custom pattern. The SRP panel allows up to 4 user
defined patterns i.e. User 1-4.The user defined patterns can only be configured via OSP software.