RSI SUPERVISION
RSI: 01
MODE: Off
↑/↓ /
→ /← /
Enter
/
Esc
This will allow the engineer to view or change line 2 of the panel
description. Use the
UP
and
DOWN
keys to change the character and
LEFT
or
RIGHT
to move the cursor. The keypad can also be used for
entry. Press
ENTER
to accept the changes.
This will allow the engineer to view or change line 3 of the panel
description. Use the
UP
and
DOWN
keys to change the character and
LEFT
or
RIGHT
move the cursor. The keypad can also be used for entry.
Press
ENTER
to accept the changes.
This will allow the engineer to view the version of panel operating software.
This option allows the engineer to enable or disable supervision for
any connected Remote Status Indicators (RSI).
RSI
number can be
selected as 1-8.
MODE
can be Off or On for each address. This will
start supervision of the RSI at that address.
14 Ov erride Release
If Override Release is selected when a release has not occurred this
message will be displayed.
This screen will be displayed if Override Release is selected when in
a released state. This allows the Release to be overridden.
If
yes
is chosen the solenoid valves will be deactivated and the Reset
Inhibit will be cancelled.
Once the solenoids have been deactivated they will not activate.
Note: Override Release does not require the Write Enable Switch to
be ON.
12. Panel Details
2. Panel ID
1 Description line 2
12. Panel Details
2. Panel ID
2 Description line 3
12. Panel Details
2. Panel ID
3 Software version
13. RSI Supervision
PANEL DESCRIPTION
LINE 2:
DESCRIPTION LINE 2
↑/↓ /
→ /← /
Enter
/
Esc
PANEL DESCRIPTION
LINE 3:
DESCRIPTION LINE 3
↑/↓ /
→ /← /
Enter
/
Esc
TWINFLEX RELEASING
SW VER: 01001
FC KEY: 3952
Override / Deactivate
The Active Release?
1. Yes 2. No
NO RELEASE
HAS OCCURED