B
Control via Ethernet (CVE)
80
Festo – EXCM-30/-40-...-PF-EN – 1603 – English
Index 240
Subindex 0
Control word
FHPP
UINT16
R/W1/W2/-/-
Control word (
è
5.2.2 Description of the control bytes CCON/CPOS)
Byte 1: control byte CCON
Byte 2: control byte CPOS
Values: 0 … 65535
Default: 0
Index 240
Subindex 1
Dependent on the operating mode
FHPP
UINT16
R/W1/W2/-/-
Record number preselection (in record selection mode)
Number of the preselected record. At the control interface, a new record can be preselected while an
old one is still active.
Record 0 (homing)
Record 1 … 31 (normal records)
Values: 0 … 31
Default: 0
Speed (in direct mode)
Speed for a direct application.
Unit: [mm/s]
Values: 0 … 65535
Default: 0
Index 303
Subindex 0
Actual position X
FHPP
SINT32
R/-/-/-/-
The current actual position in the direction of the X-axis.
Unit: [SINC] (1 mm = 1000 SINC)
Values: –2147483648 … 2147483647
Default: 0
Index 303
Subindex 1
Actual position Y
FHPP
SINT32
R/-/-/-/-
The current actual position in the direction of the Y-axis.
Unit: [SINC] (1 mm = 1000 SINC)
Values: –2147483648 … 2147483647
Default: 0
Index 304
Subindex 0
Setpoint position X
FHPP
SINT32
R/-/-/-/-
The current setpoint position X is calculated by the controller.
Unit: [SINC] (1 mm = 1000 SINC)
Values: –2147483648 … 2147483647
Default: 0