6
Diagnostics
68
Festo – EXCM-30/-40-...-PF-EN – 1603 – English
Hex
Type of error/diagnostic memory
Error name
Dec
1D
29
CAN bus communication stopped by master,
FB has master control
Can be parameterised as:
F
/-/-
Diagnostic memory: always
The CAN-Master sent “Node Stop” to the controller.
Check the system and the function of the CAN-Master.
Send “Node Start” to the controller.
– Acknowledgement option: Error can be acknowledged.
Parameterisable error response(s):
B
, C, E, F
25
37
Path calculation
Can be parameterised as:
F
/-/-
Diagnostic memory: optional
The positioning target cannot be reached through the positioning or edge condition options.
Check the parameterisation of the affected records.
Check parameterisation of the MC window.
Make sure that the drive is at rest before the start of positioning.
– Acknowledgement option: Error can only be acknowledged after eliminating the cause.
Parameterisable error response(s):
A
26
38
CAN fieldbus parameters missing
Can be parameterised as:
F
/-/-
Diagnostic memory: always
One or more CAN bus parameters are not correct.
Check the CAN bus parameters.
– Acknowledgement option: Error can be acknowledged.
Parameterisable error response(s):
B
27
39
Save parameters
Can be parameterised as:
F
/-/-
Diagnostic memory: optional
Error when writing to the internal flash memory.
Execute the last operation again. If the error remains, it means the hardware may be defective.
– Acknowledgement option: Error can only be acknowledged after eliminating the cause.
Parameterisable error response(s):
G
28
40
Homing required
Can be parameterised as:
F
/-/-
Diagnostic memory: optional
A valid reference travel has not yet been conducted.
The reference point is no longer valid (e.g. through logic voltage failure or because the axis zero point
has been changed).
Perform a homing run or repeat the last homing process if it was not completed successfully.
– Acknowledgement option: Error can only be acknowledged after eliminating the cause.
Definable error response(s):
B
, C, D, E, F, G