![background image](http://html1.mh-extra.com/html/federal-signal-corporation/ultravoice-uv/ultravoice-uv_installation-operation-and-service-manual_3830688022.webp)
22
Operations
UltraVoice (UV)
You can activate functions 1 through 7 by providing momentary, dry contact closure
between COM and the desired JP14 terminal. Shorting F1 to COM activates whatever
is programmed for code #1, shorting F2 to COM activates whatever is programmed for
code #2, and so on. A half second momentary contact duration is required.
To terminate an activated signal before it runs for the full duration, do the following:
provide a momentary contact closure between JP14 COM and F8 (RESET).
NOTE
: No matter how F8 is programmed, F8 is a master reset or a stop switch.
Table 9 Remote Activation Connections (JP14)
JP14 Terminal
Function
1—COM
Common
2—F1
F1—Activates functions 1
3—F2
F2
—
Activates functions 2
4—F3
F3
—
Activates functions 3
5—F4
F4
—
Activates functions 4
6—F5
F5
—
Activates functions 5
7—F6
F6
—
Activates functions 6
8—F7
F7
—
Activates functions 7
9—F8
F8
—
Activates functions 8
10—COM
Common (Reset)
Figure 6 UV Backplane Motherboard (JP12, JP14, and JP15)
24 Vdc Supply (JP13)
Use this output to power external equipment at 24 Vdc maximum 10 A. See Figure 7.
Charger Sense (JP20)
The charger sense (JP20) input is located on the backplane motherboard. It connects from
the charger. Greater than 3 Vdc is a pass on JP20 pin 2. See Figure 6.
JP12
JP14
JP15
Charger JP20
Содержание ultravoice UV