Series Soft Start User Manual
MAN-AGY-001. Version 04. 21/09/2018
PNU Name
Description
Options
Words Type Units Detail
119
Modbus
Enable
Enable using Modbus
On: The unit is enabled
Off: The unit is disabled
0=Off, 1=On.
1
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 1
Default: 0
120
Modbus
Start
Start / Stop using Modbus
On: Starts the Unit
Off: Stops or Soft stops the Unit
0=Off, 1=On.
1
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 1
Default: 0
121
Modbus
Reset
Reset using Modbus
On: The initial state required for a reset.
Off: The final state required for a reset.
To reset pulse high and then low
0=Off, 1=On.
1
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 1
Default: 0
143 Fire Mode A special feature that allows the Unit to
operate with ALL of the trips OFF.
Set " Cntrl Funct" to "D2 Fire Mode
”,
Enabled when D2 is high
Although the unit will keep running in this
mode it may become damaged.
In some instances the damage may inhibit
a subsequent starts
This is only to be used in an emergency
0=Off, 1=On.
1
R
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 1
Default: 0