Series Soft Start User Manual
MAN-AGY-001. Version 04. 21/09/2018
Control Terminal Connection
Control Terminal Functions
#1 24V dc Specification: 24V 10VA, residual ripple < 100Mv, spikes/switching peaks < 240mv,
#2 The voltage applied to the digital inputs D1 and D2 must not exceed 24V dc
#3 230Vac, 1A, AC15. 30Vdc, 0.5A resistive
Digital Input 2 (D2) Selectable Functions
Different functions may be assigned to Digital Input 2 in the I/O menu. Available assignments are:
Reset
Hold Start Ramp
Enable
Fire Mode (In Fire Mode all trips are disabled)
Digital Output 21/22 Selectable Functions
The output may be mapped to Fault or Top-of-Ramp indication
Terminal
Description
Function
Selectable
Note
24Vdc
Control Us
No
#1
0V
Control Supply -Us
No
COM
Digital Inputs Common
No
D1
Digital Input 1
No
#2
D2
Digital Input 2
Yes
#2
13/14
Main Contactor Control (Run
Relay)
No
#3
21/22
Fault Relay
Yes
#3
24V
COM
0V
13
D1
14
D2
22
21
Electrical Installation (continued)