13
agility
TM
Series Soft Start User Manual
MAN-AGY-001. Version 04. 21/09/2018
General Specification (continued)
As
Control
Supply input
0, 24V
Standard
supply
Kind of current, rated
frequency
d.c.
Rated voltage U
s
24Vd.c.
Maximum power consumption
12VA
Control
Programmable opto-isolated
inputs
D1, D2
circuit
Common input, marking
COM
Kind of current, rated
frequency
d.c.
Rated voltage U
c
24Vd.c.
Protect with
4A
With
Control
Supply input
L, N
UL listed
fuse
extra
Supply
Kind of current, rated
frequency
a.c., 50 - 60Hz ± 5Hz
module
Rated voltage U
s
110V to 230V a.c.
Rated input current
1A
Control
Programmable opto-isolated
inputs
D1, D2
circuit
Common input
COM
Kind of current, rated
frequency
a.c., 50 - 60Hz ± 5Hz
Rated voltage U
c
110V to 230V a.c.
Auxiliary
Form A
–
Single gap make -contact (normally
open)
13, 14
circuit
1)
Form B
–
Single gap break-contact (normally
closed)
21, 22
Utilization category, voltage rating, current
rating
Resistive load,
250Vac, 2A.
Cosø =0.5, 250Vac,
2A.
Electronic
Trip Class
10 (factory default), 20 or 30
(selectable)
overload relay
Current setting
7A to I
e
with manual reset and
thermal
Rated frequency
50 to 60Hz ± 5Hz
memory
Time-current characteristics
See ‘Motor Overload ‘cold’ trip curves’
1)
Compliant with Annex S of IEC 60947-1:2007 at 24Vd.c.
Electrical Installation (continued)