Warnings
Isolation
Caution: agility
TM
uses semiconductor devices in the main circuit and is not designed to
provide isolation. For this reason isolation means must be installed in the supply circuit in
accordance with the appropriate wiring and safety regulations
Electrical Control Supply Requirements
All electrical connections are made to power input and output terminals, control terminals
and an earth stud.
Fuse Protection
The Mains Supply and the Control Supply each require protection. Although all units have
electronic overload protection for the Soft Starter, the installer should always fit fuses, for
motor protection, between the unit and the Mains Supply, not between the unit and the motor.
Semiconductor fuses can be supplied as an option for short-circuit protection of the
semiconductors. These fuses must be fitted externally to the agility
TM
chassis to comply with
certain standards. It is the responsibility of the installer and system designer/specifier to ensure
that the required standards or regulations are not affected by so doing.
Safety
agility
TM
soft starters contain hazardous voltages when connected to the electrical power
supply. Only qualified personnel who are trained and authorized should carry out
installation, operation and maintenance of this equipment. Refer to and carefully follow all
of the ‘Warnings’ section at the
beginning of this user manual, as well as other warnings and notes
throughout the manual.
Electrical Supplies
The unit requires a 3-phase balanced Mains Supply to provide the power for the controlled motor,
and a 24Vdc for the internal control circuitry. The unit will not operate unless the control supply
voltage is within the specified limits.
Electrical Installation