15
agility
TM
Series Soft Start User Manual
MAN-AGY-001. Version 04. 21/09/2018
Short Circuit Protection
Type designation (AGY-)
101
-6
103
-6
105
-6
107
-6
109
-6
111
-6
113
-6
Rated operational current
I
e
A
17
22
29
35
41
55
66
Rated conditional short circuit
current
I
q
kA
5
5
5
5
5
5
10
Class J time-delay fuse
#1
Maximum
rating Z
1
A
30
40
50
60
70
100
125
UL Listed inverse-time delay circuit
breaker
#1
Maximum
rating Z
2
A
60
60
60
60
60
150
150
Semiconductor fuse (class aR)
#2
,
duty
≤
5 starts per hour.
Type
Mersen 6,9 URD 30 _
Bussmann 170M30__
Bussmann 170M31__
Bussmann 170M32__
SIBA 20 61___
Fuse rating
A 100A 100A 160A 160A 160A 200A 200A
Semiconductor fuse(class aR),
#2
duty
>
5 starts per hour
#3
.
Type
Mersen 6,9 URD 30 _
Mersen 6,9 URD 31 _
Bussmann 170M30__
Bussmann 170M40__
Bussmann 170M31__
Bussmann 170M41__
Bussmann 170M32__
Bussmann 170M42__
SIBA 20 61___
SIBA 20 61___
Fuse rating
A 160A 160A 200A 200A 250A 250A 250A
# 1.
Suitable For Use On A Circuit Capable Of Delivering Not More Than ___I
q
___ rms Symmetrical Amperes,
600Volts Maximum, When Protected by Class J time delay Fuses with a Maximum Rating of ___Z
1
___ or
by a Circuit Breaker with a Maximum Rating of ___Z
2
___.
# 2.
Correctly selected semiconductor fuses can provide additional protection against damage to the
agility
TM
unit (This is sometimes referred to as type 2 co-ordination). These semiconductor fuses are
recommended to provide this increased protection.
# 3.
Only when optional fan is fitted, see Rating table (Note 5).
Electrical Installation (continued)