17
agility
TM
Series Soft Start User Manual
MAN-AGY-001. Version 04. 21/09/2018
Motor Overload Protection
agility
TM
provides full motor overload protection, configurable through the user interface.
Overload trip settings are determined by the Motor Current setting and the Trip Class setting. Trip
class choices are Class 10, Class 20, and Class 30. The agility
TM
soft starters are protected using
full I
2
T motor overload with memory. See Appendix 1 for sizing guide.
Please note: When the overload has tripped, there is a forced cooling time to allow the
overload to recover before the next start.
The ‘warm’ trip times are 50% of the ‘cold’ trip time
Electrical Installation (continued)