124
agility
TM
Series Soft Start User Manual
MAN-AGY-001. Version 04. 21/09/2018
Sizing Guide
agility
Typical Applications
Standard Duty
Medium Duty
Heavy Duty
Agitator
Compressor - Centrifugal
Crusher
Compressor - Rotary Vane
Compressor - Reciprocating
Shredder
Compressor -Unloaded
Compressor - Rotary Screw
Wood Chipper
Conveyor - Unloaded
Ball Mill
Fan - High Inertia or >85A
Bow Thruster - Zero Pitch
Bow Thruster - Loaded
Fan - Low Inertia or <85A
Conveyor - Loaded
Feeder - Screw
Grinder
Lathe Machines
Hammer Mill
Mixer - Unloaded
Mills - flour etc.
Moulding Machine
Mixer - Loaded
Plastic and Textile Machines
Pelletizers
Pump - Submersible
Press, Flywheel
- Centrifugal Positive Displacement Pump
Pump - Submersible
- Reciprocating
- Rotodynamic Positive Displacement Pump
Saw - Band
- Rotary
Transformers
Pump Jack
Voltage Regulators
Rolling Mill
Roots Blower
Saw - Circular
Screen - Vibrating
Tumblers
Trip Class
Trip Class 10
Trip Class 20
Trip Class 30
Rated Starting Capability
3x Motor Current - 23secs
4x Motor Current - 19secs
4x Motor Current - 29secs
3.5x Motor Current - 17secs
Max Starts per Hour
5 starts/hour
5 starts/hour
5 starts/hour
with Optional Cooling Fan
40 starts/hour
40 starts/hour
40 starts/hour
Height Above Sea Level Standard operating height is 1000m, for every 100m increase motor Amps/kW by 1%, up to 2000m.
Example: For a 20A motor at 1500m make model selection based on 21A (5% higher)
Operating Temperature Standard operating temperature is 40degC, for every 1degC above, increase motor Amps/kW by 2%, up to 60degC.
Example: For a 20A motor at 50degC make model selection based on 24A (20% higher)
Increased Starts per Hour Fit optional fan to increase maximum up to 40 starts per hour.
Step 1
- Select the
application from the
list and follow that
column down.
Step 2
- Confirm the
rated starting
capability of the soft
start against the
application.
Step 3
- Consider the
operating
environment and
make the model
selection on a higher
amp rating.
agility is not suitable for
very high inertia loads
such as centrifuges,
loaded crushers or start
times >30s.