Working level
for normal daily operation
Adjustment to safety elements
r10
Safety switch butterfly valve
(F40) see section .2
9
(Default 0)
Parameter is hidden, if parameter [A40] = 2 or 3
0: no safety switch
1: prevents the start of cooling / cleaning,
when switch is not in proper position
2: as + abort of cleaning when switch in the wrong position
1
r11 Cleaning pump monitoring via pressure switch
(Fault F41)
(Default
)
10
For dry running protection of the cleaning pump (open in case of fault)
0: deactivated
1 .. 20: Stop cleaning after x seconds without pressure
r12 Cleaning pump fault thermo contact switch
(Fault F42)
(Default 0)
To protect the cleaning pump (open in case of fault)
0: no thermo contact switch
1: thermo contact switch active
r18
(Default 0)
Activation of compressor in the final rinse
0: deactivated
1: activated. (In purging step n84, compressor is activated when the tank
temperature is between 40°C and 4 °C)
Detergent options
r20 Dosing position
(see section
and .15)
6.2
9
(Default 2)
0: dosing in feed container (displacement cleaning)
in cleaning diagram
1: position D1
2: position D2 in cleaning diagram
r21 Detergent sequence in case of 3-cycles
(Default )
1
(if second main cleaning stage is deactivated)
0: only alkaline
1..10: x times alkaline, before one time acid
r23 Setting of drain valve in pre-rinse 2 during filling via water reservoir
0: drain valve closed, 1: drain valve opened
1
(Default )
Drain valve settings
r24
drain valve 1
Switching mode
(Default )
1
0: normally closed 1:
open
currentless
r25
drain valve 2
Switching mode
(Default 0)
0: normally closed 1:
open
currentless
Switch to level
“Extended cleaning parameters”
See section 8.1.
r parameters
Code: C567
General cooling parameters
code: C212
Extended cooling parameters
code: D345
General cleaning parameters
code: B454
Extended cleaning parameters
code: C567
Service parameter
s
code: EA03
General tank monitor parameters
code: 4711
Extended tank monitor parameters
code: F94A
Alarm configuration
code: FFFF
Configuration
code: A384
I/O test parameters
code: 10E5
8.5 Level “Extended cleaning parameters” (r parameters)
8. Setting of parameters
Page 54