OLH
Out maximum limit (in % of the out).
Span:
- From 0 to 100 when the instrument is
configured with one control out.
- From -100 to 100 when the instrument
is configured for two control outs.
tOL
Duration of the out power limiter (in
minutes).
Available only if Pb is not 0.
Span: from 1 to 540 min. Above this limit,
the display shows "
Inf
" and the
limitation is always entered.
NOTE
NOTE
NOTE
NOTE
NOTE: Parameter tOL can be modified
but the new value will only become
operative at the next instrument start up
unless the new value is
Inf
.
6 .
6 .
6 .
6 .
6 . ERROR MESSAGES
ERROR MESSAGES
ERROR MESSAGES
ERROR MESSAGES
ERROR MESSAGES
6.1
6.1
6.1
6.1
6.1 MEASUREMENT ANOMALY SIGNAL
MEASUREMENT ANOMALY SIGNAL
MEASUREMENT ANOMALY SIGNAL
MEASUREMENT ANOMALY SIGNAL
MEASUREMENT ANOMALY SIGNAL
The instrument display (the upper display for
model 0316) shows the OVERRANGE and
UNDERRANGE conditions with the following
indications:
Overrange
Underrange
The example shows the display of model 0316.
Model 0216 displays 4 digits.
The sensor break can be signalled as:
- for TC/mV input
: OVERRANGE or
UNDERRANGE selected
by a solder jumper
- for RTD input
: OVERRANGE
On RTD input, a special test is provided to signal
OVERRANGE when input resistance is less than
12 ohm (Short circuit sensor detection).
NOTE
NOTE
NOTE
NOTE
NOTE:
When:
- The instrument is set for one control out only
and an OVERRANGE is detected, the OUT 1
turns OFF (if reverse action) or ON (if direct
action).
- The instrument is set to use two control outs
and an OVERRANGE is detected, OUT 1 turns
OFF and OUT 2 turns ON.
- The instrument is set for one control out only
and an UNDERRANGE is detected, the OUT 1
turns ON (if reverse action) or OFF (if direct
action).