7
GB
GB
GB
GB
GB
numerical value (or the selection code). In the
model 0216, the display shows the parameter
code and the numerical value alternatively.
To alter the value set or the option selected press
or and confirm with .
The parameter for loading the default parameters
is shown in section B at the end of the manual.
4.4
4.4
4.4
4.4
4.4 CONFIGURATION PARAMETERS
CONFIGURATION PARAMETERS
CONFIGURATION PARAMETERS
CONFIGURATION PARAMETERS
CONFIGURATION PARAMETERS
P1 - Type of input and standard range
P1 - Type of input and standard range
P1 - Type of input and standard range
P1 - Type of input and standard range
P1 - Type of input and standard range
Type of input
Range
0 TC type L
0 / +900 °C
1 TC type J
0 / +999 °C
(0316)
0 / +1000 °C
(0216)
2 TC type K
0 / +999 °C
(0316)
0 / +1370
(0216)
3 TC type N
0 / +999 °C
(0316)
0 / +1400 °C
(0216)
4 RTD type Pt 100
-199 / +800 °C
(0316)
-200 / +800 °C
(0216)
5 RTD type Pt 100
-19.9 / +99.9 °C
(0316)
-199.9 / +400.0 °C
(0216)
6 TC type T
0 / +400 °C
8 TC type L
0 / 999 °F
(0316)
0 / 1652 °F
(0216)
9 TC type J
0 / 999 °F
(0316)
0 / 1832 °F
(0216)
10 TC type K
0 / 999 °F
(0316)
0 / 2498 °F
(0216)
11 TC type N
0 / 999 °F
(0316)
0 / 2552 °F
(0216)
12 RTD type Pt 100
-199 / 999 °F
(0316)
-328 / 1472 °F
(0216)
13 TC type T
0 / 752 °F
parameters (SP, SP2 and t can always be
modified).
If the modification of the parameters has been
enabled, the passage in configuration is free.
If not it will be allowed by entering, when
requested, the numerical value programmed in
P11, or master key code.
P11 = 500/999
P11 = 500/999
P11 = 500/999
P11 = 500/999
P11 = 500/999 As for the previous point, with the
difference that alarm thresholds (AL and AL2) can
be modified as well as SP, SP2 and t.
In the two previous cases, with P14 = On, the
parameters set as not modifiable can however be
displayed. With P14 = OFF they are not.
To set P11 and P14 see section 4.4.
4.3
4.3
4.3
4.3
4.3 ACCESS TO THE CONFIGURATION
ACCESS TO THE CONFIGURATION
ACCESS TO THE CONFIGURATION
ACCESS TO THE CONFIGURATION
ACCESS TO THE CONFIGURATION
PROCEDURE
PROCEDURE
PROCEDURE
PROCEDURE
PROCEDURE
To access the configuration, press and
simultaneously (press first and immediately
afterwards ) keeping both the pushbuttons
pressed for three seconds.
In the model 0316 the lower display will show
Cnf
,
the upper
OFF
. In model 0216
OFF
and
CnF
will
appear alternatively.
Press or within 10 seconds to set
ON
, then
confirm with .
If the device is in the protected condition (see
previous section), the lower display (0316) shows
Cnf
, the upper a dashed line (instead of
OFF
). In
model 0216 the two wordings appear alternately.
By means or enter the value entered in P11,
or master key value. Press to confirm.
The instrument is now in configuration mode, and
the display shows
Cnf
steadily for both models.
Via we advance to the first parameters.
In configuration, the lower display shows the code
of the parameter (P1-P28), the upper the
02-0316-1-DER.pmd
22/04/2004, 16.19
7
Содержание 216
Страница 39: ...B 5 216 316 A 00NEW pmd 22 04 2004 15 18 5 ...