Param. Description
SP
Set point (in eng. units).
Span: from rL to rH.
n.rS
Manual reset of the alarms.
This parameter is displayed if one alarm
has been programmed with manual
reset.
Set ON and press the pusbutton to
reset the alarms.
Sts
SP/SP2 or TIMER CONTROL
OFF
SP2
Set point 2 (in eng. units).
This parameter is present if P27 = 1, 2,
3, 4 or 5.
Span: from rL to rH.
t
time of the timer function (in minutes
and seconds).
This parameter is present if P27 greater
than 2.
Span: from 10 seconds (00.1) to 90
minutes (90.0).
nnn
Software key for parameter protection.
This parameter is skipped if P11 = 0 or 1.
ON = the instrument is in LOCK
condition
OFF = the instrument is in UNLOCK
condition.
To switch from LOCK to UNLOCK, set a
value equal to the value of parameter
P11.
To switch from UNLOCK to LOCK, set a
value different from the value of
parameter P11.
Span: 2/999
AL.1
Alarm 1 threshold (in eng. units).
This parameter is available only if
P5 = 1, 2 or 3.
Spans:
- From P2 to P3 for process alarm
(P5 = 1)
- From 0 to 500 units for band alarm
(P5 = 2).
- From -199 to 500 units for deviation
alarm (P5 = 3).
HS.1
Alarm 1 hysteresis (in % of P3 - P2
span).
This parameter is available only if
P5 = 1, 2 or 3.
Span: From 0.1% to 10.0% of the input
span or 1 LSD.
NOTE
NOTE
NOTE
NOTE
NOTE: If the hysteresis of a band alarm
is larger than the alarm band, the
instrument will use an hysteresis value
equal to the alarm band minus 1 digit.
AL.2
Alarm 2 threshold (in eng. units).
This parameter is available only if
P22 = 1, 2 or 3.
Spans:
- From P2 to P3 for process alarm
(P5 = 1)
- From 0 to 500 units for band alarm
(P5 = 2).
- From -199 to 500 units for deviation
alarm (P5 = 3).
HS.2
Alarm 1 hysteresis (in % of P3 - P2
span).
This parameter is available only if
P22 = 1, 2 or 3.
Span: From 0.1% to 10.0% of the input
span or 1 LSD.
NOTE
NOTE
NOTE
NOTE
NOTE: If the hysteresis of a band alarm
is larger than the alarm band, the
instrument will use an hysteresis value
equal to the alarm band minus 1 digit.
Pb
Proportional band (in % of P3 - P2 span).
Span:
- For one control output: from 1.0% to
99.9% (from 1.0% to 100.0% for
model 0216) of the input span (P3-P2).