12) Parameter group 500: Fixed frequencies, automatic cycling frequencies
12) Parameter group 500: Fixed-frequency, automatic cycling frequencies
Up to 15 fixed-frequencies are selectable on E800 inverters, including individual ramp and direction setting.
Automatic cycling sequence for up to 8 fixed-frequencies can be set, including ramp, direction, run- and pausing time.
Set parameter
F203=4
(
F204=4
), to select fixed frequency mode:
F500
Fixed-frequency
mode selection
Selection:
0
: 3 Fixed frequencies are available
1
: 15 Fixed frequencies available, binary coded (K1, K2, K3, K4 - terminal)
2
: Up to 8 Fixed frequencies – auto-cycling mode
Default: 1
F203 F500
Fixed frequency mode
Description
4 0
3 Fixed frequencies
direct selection
To combine with analogue control, fixed-frequencies have
priority
4 1
15 Fixed frequencies
binary selection
To combine with analogue control, fixed-frequencies have
priority
4 2
Up to 8 auto-cycling fixed
frequencies
Independent mode, no manual frequency control is possible during
cycle, except STOP command –
F501, F502, F503
are the auto-
cycling parameters
Auto-cycling parameter:
F501
Number of different frequencies for
auto-cycling function
Selection: 2…8
Default setting: 7
F502
Number of automatic cycles
Range: 0….9999
0 = Endless cycling
Default setting: 0
F503
Status after cycle completed
Selection: 0: Stop
1: Keep last valid frequency
Default setting: 0
Programming of the individual fixed-frequencies:
Accelerati
on ra
mp
fixed
-freq
uen
ci
es
1 - 15 (0,1....300
0sec.)
(d
ef
aul
t)
Decelerati
on ra
mp
fixed
-freq
uen
ci
es
1 - 15 (0,1....300
0sec.)
(d
ef
aul
t)
Rota
tio
n
direc
tion
fixed
-freq
uen
ci
es
1 - 15 –
(
0=FWD
, 1=REV
)
Aut
o
-cycl
e -
dur
ation
for fix
e
d-
freq
ue
ncies
1 - 8 (0,
1....3000
sec.)
(1
sec.)
Aut
o
-cycl
e – pa
usin
g ti
me
for fix
e
d-
freq
ue
ncies
1 - 8 (0,
1...3000s
ec.)
(0s
ec.)
Default setting:
Accel./Decel. time,
depending on
inverter model
0.2 - 4.0KW: 5.0 sec.
5.5 - 30KW: 30.0 sec.
>30kW: 60 sec.
F504
Fixed-frequency 1 (Hz)
F519 F534
F549
F557
F565
Default: 5.00Hz
F505
Fixed-frequency 2 (Hz)
F520 F535
F550
F558
F566
Default: 10.00Hz
F506
Fixed-frequency 3 (Hz)
F521 F536
F551
F559
F567
Default: 15.00Hz
F507
Fixed-frequency 4 (Hz)
F522 F537
F552
F560
F568
Default: 20.00Hz
F508
Fixed-frequency 5 (Hz)
F523 F538
F553
F561
F569
Default: 25.00Hz
F509
Fixed-frequency 6 (Hz)
F524 F539
F554
F562
F570
Default: 30.00Hz
F510
Fixed-frequency 7 (Hz)
F525 F549
F555
F563
F571
Default: 35.00Hz
F511
Fixed-frequency 8 (Hz)
F526 F541
F556
F564
F572
Default: 40.00Hz
F512
Fixed-frequency 9 (Hz)
F527 F542
F573
Default: 5.00Hz
F513
Fixed-frequency 10
F528 F543
F574
Default: 10.00Hz
F514
Fixed-frequency 11
F529 F544
F575
Default: 15.00Hz
F515
Fixed-frequency 12
F530 F545
F576
Default: 20.00Hz
F516
Fixed-frequency 13
F532 F546
F577
Default: 25.00Hz
F517
Fixed-frequency 14
F532 F547
F578
Default: 30.00Hz
F518
Fixed-frequency 15
F533 F548
F579
Range for
F504 – F518
:
F112 .......F 111
Default: 35.00Hz
E800 – Rev.01 -EN- SOFT Rev. 2.04
© 2015 EURADRIVES EUROPE GmbH
- 51 -