8) Parameter group 100: Basic parameters
8)
Parameter group 100: Basic parameters
F100
Password
Range: 0 – 9999
Werkspasswort: 8
-If F107=1 (password enabled): enter correct password, to unlock parameter modification function. Incorrect password results in
Err1
on the display
F102
Rated inverter current (A)
Range: 1.0 – 800.0
Factory set, depending on model, read only
F103
Rated inverter power (KW)
Range: 0.2 – 800.0
Factory set, depending on model, read only
F105
Software Version No.
Range: 1.00 - 10.00
Factory set, depending on model, read only
(2.04)
F106
Control algorythm
Selection: 2: V/Hz
3: Reserved
4: Reserved
5: Reserved
6: Synchronus motor control *
Default setting: 2
2: V/Hz Modus funktioniert auch bei mehreren parallel geschalteten Motoren
6: * Optional software for synchronus motor comtrol (permanent magnet motor)
Attention!!
All motor parameters must be set precisely, to guarantee correct function. Especially in syncronus motor control mode
(F106=6) we recommend to run the AUTOTUNING routine (see: parameter group 800)
The V/Hz mode is recommendet for simple drives, including applications with quadratic torque characteristic (pump –
fan). F137 defines the different V/Hz characteristics
Inverter rated power should match the motor power
F107
Activation of password
protection (for parametrizing)
Selection: 0: No password protection
1: Password protection
Default setting: 0
F108
Password setting
Range: 0 - 9999
Default setting: 8
F109
Start – frequency (Hz)
Range: 0.00 - 10.00 Hz
Default setting: 0.00 Hz
F110
Start – frequency duration (sec.)
Range: 0.0 - 10.0 sec.
Default setting: 0.0 sec.
The inverter always starts running with the selected Start-frequency, if the target frequency is lower than the Start-frequency,
F109
will be ignored.
After the inverter gets a START command, it will remain at the Start-frequency, (set in
F110),
for the time, set in
F111.
After the
delay, it will proceed with the acceleration ramp to reach the final frequency. The acceleration ramp does not take into account
the start frequency delay time
The Start-frequency value is independent and not limited by the minimum frequency
F112.
In case
F109
is lower, than
F112,
the
inverter will start running with the values in
F109
and
F110
. After the inverter reached the minimum frequency
F112
, the values
F111
and
F112
are considered as frequency limits.
It is recommended, to chose Start-frequency lower than maximum frequency
(F111)
.
F111
Maximum frequency (Hz)
Range: F113 - 650.0 Hz
Default setting: 50.00Hz
F112
Minimum working frequency (Hz)
Range: 0.00 - F113 Hz
Default setting: 0.50Hz
The parameter
F111
limits the inverter output frequency
In SENSORLESS VECTOR mode it is recommended to limit the maximum frequency to 150 Hz
The parameter
F112
defines the minimum allowed output frequency. If speed reference corresponds to frequency lower than
the value in
F112
, the inverter stops.
WARNING!! Continuous operation at low speed may overheat the motor – forced ventilation is recommend