11) Parameter group 400: Analogue I/O channel configuration
Same configuration for
AI2
and
AI3
(= keypad potentiometer)
F406
Range definition
AI2
– lower limit (V)
Range 0.00V…F402
Default setting: 0.00V
F407
Assignation lower limit
AI2
Range: 0…F403
Default setting: 1.00
F408
Range definition
AI2
– upper limit (V)
Range: F400…10.00V
Default setting: 10.00V
F409
Assignation upper limit
AI2
Range: (1.00, F401)…2.00
Default setting: 2.00
F410
Gainfactor
AI2
(%)
Range: 0.0…10.0
Default setting: 1.0
F411
Filter factor
AI2
Range: 0.1…10.0
Default setting: 0.10
F412
Range definition
AI3
– lower limit (V)
Range 0.00V…F402
Default setting: 0.00V
F413
Assignation lower limit
AI3
Range: 0…F403
Default setting: 1.00
F414
Range definition
AI3
– upper limit (V)
Range: F400…10.00V
Default setting: 10.00V
F415
Assignation upper limit
AI3
Range: (1.00, F401)…2.00
Default setting: 2.00
F416
Gainfactor
AI3
(%)
Range: 0.0…10.0
Default setting: 1.0
F417
Filter factor
AI3
Range: 0.1…10.0
Default setting: 0.10
F418
0 HZ Dead band 0 Hz
AI1
Range: +/- 0…0.50V
Default setting: 0.00
F419
0 HZ Dead band 0 Hz
AI2
Range: +/- 0…0.50V
Default setting: 0.00
F420
0 HZ Dead band 0 Hz
AI2
Range: +/- 0…0.50V
Default setting: 0.00
0 Hz dead band: If frequency crosses 0Hz range (depending on signal range setting), 0 Hz output frequency will
result, within the 0 Hz dead band.
Panel / potentiometer selection (inverter with remote keypad / keypad potentiometer
option)
F421=1
Remote operation panel selected, the integrated panel is deactivated, including potentiometer (regardless setting
on
F422
).
F421
Operating panel
Selection: 0=Integrated panel,
1=Remote panel
Default setting: 0
F422
Potentiometer
Selection: 0=Integrated panel potentiometer
1=Remote panel potentiometer
Default setting: 0
This configuration can not be reset to factory default (via
F160
)
Higher hysteresis value will result in a more stable system, but with longer reaction time on changing speed reference
signal
F437
Analog filter hysteresis
Range: 1…100
Default setting: 10
E800 – Rev.01 -EN- SOFT Rev. 2.04
© 2015 EURADRIVES EUROPE GmbH
- 48 -