8) Parameter group 100: Basic parameters
F136
Slip compensation in V/Hz mode
Range: 0 - 10%
Default setting: 0
- This parameter compensates the load-depending slip of the asynchronus motor – it works only in the stable area of the motor
speed/torque characteristic
- during the "catch on the fly" process this function is deactivated
F137
Motor voltage increase in the
low frequency range (for V/Hz
mode only)
Selection: 0:
Linear
1:
Quadratic
2:
User defined (6 - Point)
3: Automatic
Default setting: 3
F138
Lineare increase
Range:
1 - 20
Werk: 0.2-3.7 kW : 7
5.5-30 kW : 6
37-75 kW : 5
> 90 kW: 3
F139
Quadratic increase
Selection:
1 - 6
Default
setting:
1
Voltage increase on low frequencies is necessary to compensate the
stator copper resistance.
With
F137=0
linear
voltage increase is chosen, suitable for constant
torque load.
Voltage increase
linear
/
quadratic
/
BOOST
f
Knee-frequency
U
16
1
6
1
F141
F140
F137=1
quadratic
increase, the right curve for load with quadratic
characteristic, like pump and fan.
F137=2,
serves to possible to program a user specific V/Hz curve – see table below
A total of 12 parameter are necessary to define the user specific curve
(F140 bis F151)
.
F140
User defined frequency F1
Range: 0 - F142
Default setting: 1.00
F141
Assigned motor voltage V1
Range: 0 - 100
%
Default
setting:
4
F142
User defined frequency F2
Range:F140 - F144
Default setting: 5.00
F143
Assigned motor voltage V2
Range: 0 - 100
%
Default
setting:
13
F144
User defined frequency F3
Range: F142 - F146
Default setting: 10.00
F145
Assigned motor voltage V3
Range: 0 - 100
%
Default
setting:
24
F146
User defined frequency F4
Range: F144 - F148
Default setting: 20.00
F147
Assigned motor voltage V4
Range: 0 - 100
%
Default
setting:
45
F148
User defined frequency F5
Range: F146 - F150
Default setting: 30.00
F149
Assigned motor voltage V5
Range: 0 -100
%
Default
setting:
63
F150
User defined frequency F6
Range: F148 - F118
Default setting: 40.00
F151
Assigned motor voltage V6
Range: 0 - 100
%
Default
setting:
81
Remark: V1<V2<V3<V4<V5<V6
,
F1<F2<F3<F4<F5<F6.
Voltage (%)
V6
V5
V4
V3
V2
If
F137=3,
the slip compensation works in automatic – correct setting
for all motor parameter is necessary to guarantee correct operation –
AUTOTUNING may be used to find motor parameters, like
inductance and stator resistance (see parameter group 8).
V1
F1 F2 F3 F4 F5 F6 Frequency (Hz)
User p
WARNING!! High voltage BOOST on low speed
may result in inverter over-current trip and/or
motor overheating
rogrammable curve
E800 – Rev.01 -EN- SOFT Rev. 2.04